2.5

Start-Up and Commissioning

During Start-Up and Commissioning, DISABLE all outputs from the Detector to any control panels or control
devices. As with any flame and fire detector, after the Detector(s) is powered, perform an external Detector
test "end to end". Using an external hand-held test lamp ensures that the Detector has a clear unobstructed
view of the threat area and the wiring is correct to the control panel or device.
Note:
Honeywell Analytics FSX Detectors feature an automatic built-in "through the lens" test that
verifies the cleanliness of its viewing window lens and test its internal electronics and
software. As with any optical fire and flame detector, this does not constitute a fully
functional "end to end" test as these types of internal self-tests only partially check and test
the operational readiness of a detector.
In order to test the full functionality and operational readiness of any fire or flame detector
"end to end", without starting a real fire (which is not permitted in hazardous areas), it is
necessary to test the detector(s) with an external test lamp.
Using a test lamp is the only non-hazardous and safe method to test any flame or fire
detector's sensors, internal electronics and its alarm activation software, viewing window lens
cleanliness, terminal wiring integrity, actual relay activation, and the proper functionality of
any other outputs that are used. Also, since most detectors are installed in a fire alarm
system, this is the only method to test the complete fire alarm system, ensuring all the system
wiring and cabling and system control panel are properly installed.
Additionally, using an external test lamp eliminates the following detector conditions:
1. The fire or flame detector(s)' window lens being covered up (such as paint, paint over
spray, paint masking material, hanging garments, etc.),
2. Improperly positioned and oriented for coverage of the threat area,
3. Partial or full blockage of the detector's line of sight by one or more objects (i.e., recently
installed air ducts or pipes, storage boxes, vehicles, etc.) such that the threat area is not
fully protected. Since all optical fire and flame detectors are line-of-sight sensors, they
must be properly positioned and oriented with an unobstructed view of the threat area so
that they can detect flames/fires.
To test the full functionality of a FSX Detector, use the Model TL-1055 or TL-2055 Test Lamp in
the manner prescribed in this Instruction Manual.
WARNING: Use test lamp model TL-1055 in non-hazardous locations only! For hazardous locations,
use model TL-2055, as described below.
The TL-1055 and the TL-2055 are the only Test Lamps that will activate the FSX Detectors..
Additionally, do not use these Test Lamps to activate other Honeywell Analytics Detectors (nor
any other conventional fire and flame detectors). Do not use other Honeywell Analytics Test
Lamps or non-Honeywell Analytics Test Lamps to test the FSX Detectors.
TL-1055 Hand Held Test Lamp (NEMA 1)
Honeywell
Figure 2-13
Installation and Operating Manual
Figure 2-14
TL-2055 Hand Held Test Lamp for Hazardous Areas
16