Figure 3-1: Examples Of Incorrect Transmitter Positioning - Honeywell XYR 5000 Series User Manual

Wireless dual discrete input transmitter, 900 mhz ism band
Hide thumbs Also See for XYR 5000 Series:
Table of Contents

Advertisement

Honeywell Industrial Wireless
Warning! During installation do not apply force to the
instrument housing or antenna. Use a proper wrench for all
installations. Failure to use correct installation procedures can
cause damage to the Transmitter.
Rev 5
08/06
Only place the Transmitter in ambient operating temperatures of
-40°F to 185°F (-40°C to 85°C).
Figure 3-1, shown below, gives examples of incorrect setups
according to the previously mentioned parameters.

Figure 3-1: Examples of Incorrect Transmitter Positioning

Because there are so many setup possibilities we cannot cover
them all. A correct setup would make sure that the above warnings
are heeded, and that the Transmitter and Base Radio are capable of
communication. The RF Placement Test section will help you to
determine if you have selected the correct installation points and
orientations for your application.
3.1.1.1 Technique for Close Positioning of Transmitters
Transmitters may be placed closely together by carefully following
this procedure. If this procedure is not followed, the communication
range of the Transmitters will be significantly reduced and the
Transmitters may eventually lose communication with the Base
Radio entirely. This procedure is easy to implement, but please read
carefully for a full understanding.
The Base Radio synchronizes with the Transmitters in synch groups
of 7,organized by their RF ID numbers. If you want to place two
Transmitters closer than 6 feet, make sure that you have set them in