Event Log Full Report Code
∗ ∗ ∗ ∗ 89
See box above field *59 for report code
entries.
∗ ∗ ∗ ∗ 90
Event Log Enables
0 = None
1 = Alarm/Alarm Restore
2 = Trouble/Trouble Restore
4 = Bypass/Bypass Restore
8 = Open/Close.
Example: To select "Alarm/Alarm
Restore", and "Open/Close", enter 9 (1
+ 8)
To select all, enter #15.
Option Selection / Remote
∗ ∗ ∗ ∗ 91
Interactive Services (RIS) Enable
Entry 1: Options
0 = None
1 = Bell Supervision Processing
4 = AAV
8 = Exit Delay Restart/Reset†
#+12 = AAV and Exit Delay
Restart/Reset
Entry 2: Remote Interactive Services
(RIS) enable
0 = RIS disabled
1 = not applicable
2 = RIS enabled
V20PSIA/V15PSIA:
Entry 1 Options: Same as above.
Entry 2 Call Waiting Disable / RIS
Enable:
0 = call waiting not used
1 = use call waiting disable digits
(∗70) entered in field ∗40; (when
selected, the system dials the
entry in ∗40 only on alternate dial
attempts; this allows proper
dialing in case call waiting
service is later canceled by the
user).
2 = RIS (Remote Interactive
Services) enabled
3 = Call Waiting disable and RIS
enabled
∗ ∗ ∗ ∗ 92
Phone Line Monitor Enable
Entry 1::
0 = disabled, 1-15 = 1 min - 15 min
(#+10 = 10 min; #+11 = 11 min;
#+12 = 12 min; #+13 = 13 min;
#+14 = 14 min; #+15 = 15 min)
Entry 2:
0 = Keypad display when line is faulted
1 = Keypad display plus keypad trouble
sound. Each partition turns off its
own trouble sound. No automatic
timeout.
2 = Same as "1", plus programmed
output device STARTS. If either
partition is armed, external sounder
activates also. External sounder
will be turned off by normal bell
timeout, or by security code plus
OFF from either partition (it need
not be the one that was armed).
|
[00]
If an Event Logging selection is made in field ∗90, a message can be
sent to the central station receiver when the log is 80% full. If the log
becomes full, new messages overwrite the oldest messages in the log.
[3]
This system can record various events in a history log (VISTA-20P =
100 events; VISTA-15P = 50 events). At any time, the downloader
operator can then upload the log and view or print out all or selected
categories of the log, or can clear the log. Event log can also be viewed
at an alpha keypad. The display/printout at the central station will show
the date, time, event, and description of the occurrences.
Data Entry Example: To select Alarm/Alarm Restore" and
"Open/Close", enter 9 (1+ 8); to select all events, enter #15.
NOTE : System messages are logged when any non-zero entry is made.
[8, 0]
Options
RIS Enable
V20PSIA/V15PSIA: Call Waiting Disable / RIS Enable
IMPORTANT: AAV should not be used when Paging or Alarm Reports
are sent to a secondary number unless the monitoring zone option is
used (which pauses calls). Otherwise, the call to the secondary number
by the communicator after the alarm report will prevent the AAV from
taking control of the telephone line, and the AAV "Listen in" session
cannot take place.
UL: for AAV, must use ADEMCO UVCM module or Honeywell AVS system;
Exit Delay Restart/Reset must be disabled
SIA Guidelines: Exit Delay should be enabled.
† "Exit Delay Restart/Reset" option allows use of the [∗] key to restart
the exit delay at any time when the system is armed STAY or
INSTANT. This feature also enables automatic exit delay reset, which
resets exit delay if the entry/exit door is re-opened and closed before
exit delay time expires after arming AWAY. Automatic Exit Delay Reset
occurs only once during an armed AWAY period.
Remote Interactive Services (RIS) Enable: This option enables
enhanced Remote Interactive Services (RIS), if supported by the
communication service in use. If enabled, device address 25 is
automatically assigned.
Bell Supervision Note: If a high impedance sounding device is used
(ex. 745X3), the bell supervision resistor (included) must be installed
at the device.
[0,0]
1
2
Entry 1: Sets the length of time a phone line fault must remain after
detected before the second digit option is activated.
Entry 2: Selects the desired phone line fault response.
Option 2 may be used even if a relay unit or Powerline carrier device is
not connected to the control.
Programmed Output Device must either be programmed to be
STOPPED in field ∗80 or STOPPED by entry of [security code] + [#] + 8
+ device number. Partition in ∗80 should be set to "0," for STOP.
UL: Field *92 must be enabled for fire alarm installations, UL commercial
burglar alarm installations and UL residential burglar alarm installations.
If the control unit is used on a UL commercial burglar alarm system which
requires 2 methods of remote communication, then the control unit's DACT
and the other method of signal transmission must monitor each other against
communication failure and line fault. The fault must be received and
annunciated within 200 seconds of its occurrence.
– 12 –