About Drive Programming
2.
Scroll to parameter group E-## Digital In/Out and
press [OK].
3.
Scroll to parameter group E-0# Digital Inputs and
press [OK]
4.
Scroll to E-01 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
5.4 International/North American Default
Parameter Settings
Setting K-03 Regional Settings to [0]International or [1]
North America changes the default settings for some
parameters. Table 5.1 lists those parameters that are
effected.
Parameter
International
Default Parameter
Value
K-03 Regional
International
Settings
K-71 Date Format
DD-MM-YYYY
K-72 Time Format
24h
P-07 Motor Power
See Note 1
[kW]
P-02 Motor Power
See Note 2
[HP]
F-05 Motor Rated
230V/400V/575V
Voltage
AF-600 FP Operating Instructions
F-04 Base
Frequency
F-53 Maximum
Reference
F-54 Reference
Function
F-17 Motor Speed
High Limit [RPM]
See Note 3
F-15 Motor Speed
High Limit [Hz]
See Note 4
F-03 Max Output
Frequency 1
H-73 Warning
Speed High
E-03 Terminal 27
Digital Input
E-24 Function Relay Alarm
AN-15 Terminal 53
High Ref./Feedb.
Value
AN-50 Terminal 42
Output
H-04 Auto-Reset
(Times)
AP-85 Speed at
Design Point [RPM]
See Note 3
AP-86 Speed at
Design Point [Hz]
FB-04 Fire Mode
Max Reference
Table 5.1 International/North American Default Parameter Settings
Note 1: P-07 Motor Power [kW] is only visible when
K-03 Regional Settings is set to [0] International.
Note 2: P-02 Motor Power [HP], is only visible when
K-03 Regional Settings is set to [1] North America.
North American
Note 3: This parameter is only visible when K-02 Motor
Default Parameter
Speed Unit is set to [0] RPM.
Value
Note 4: This parameter is only visible when K-02 Motor
North America
Speed Unit is set to [1] Hz.
Changes made to default settings are stored and available
MM/DD/YYYY
for viewing in the quick menu along with any
12h
programming entered into parameters.
See Note 1
5.4.1 Parameter Data Check
See Note 2
1.
208V/460V/575V
2.
Parameter
International
Default Parameter
Value
50Hz
50Hz
Sum
1500RPM
50Hz
100Hz
1500RPM
Coast inverse
50
Speed 0 - HighLim
Manual reset
1500RPM
50Hz
50Hz
Press [Quick Menu].
Scroll to Q5 Changes Made and press [OK].
North American
Default Parameter
Value
60Hz
60Hz
External/Preset
1800RPM
60Hz
5
120Hz
1800RPM
External interlock
No alarm
60
Speed 4-20mA
Infinite auto reset
1800RPM
60Hz
60Hz
31
5