Control Terminal Programming Examples; International/North American Default Parameter Settings - GE AF-600 FP Series Design And Installation Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

About Programming
5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
Each terminal has specified functions it is capable
of performing
Parameters associated with the terminal enable
the function
See Table 2.6 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in K-03 Regional Settings.)
The following example shows accessing Terminal 18 to see
5
5
the default setting.
1.
Press [Main Menu] twice, scroll to Parameter Data
Set and press [OK].
Illustration 5.9 AN-15 Terminal 53 High Ref./Feedb. Value
2.
Scroll to parameter group E-## Digital In/Out and
press [OK].
Illustration 5.10 Digital In/Out
3.
Scroll to parameter group E-0# Digital Inputs and
press [OK]
4.
Scroll to E-01 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
36
TM
AF-600 FP
Design and Installation Guide
Illustration 5.11 Digital Inputs
5.4 International/North American Default
Parameter Settings
Setting K-03 Regional Settings to [0] International or [1]
North America changes the default settings for some
parameters. Table 5.1 lists those parameters that are
effected.
Parameter
K-03 Regional
Settings
P-07 Motor Power
[kW]
P-02 Motor Power
[HP]
F-05 Motor Rated
Voltage
F-04 Base
Frequency
F-53 Maximum
Reference
F-54 Reference
Function
F-17 Motor Speed
High Limit [RPM]
See Note 3 and 5
F-15 Motor Speed
High Limit [Hz]
See Note 4
F-03 Max Output
Frequency 1
H-73 Warning
Speed High
E-24 Function Relay Alarm
AN-15 Terminal 53
High Ref./Feedb.
Value
DET-768b
International
North American
default parameter
default parameter
value
value
International
North America
See Note 1
See Note 1
See Note 2
See Note 2
230 V/400 V/575 V
208 V/460 V/575 V
50 Hz
60 Hz
50 Hz
60 Hz
Sum
External/Preset
1500 PM
1800 RPM
50 Hz
60 Hz
100 Hz
120 Hz
1500 RPM
1800 RPM
No alarm
50
60