Wiring To Control Terminals - GE AF-600 FP Operating Instructions Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Installation
Connector 4 is a USB port available for use with
the DCT-10
Also provided are two Form C relay outputs that
are in various locations depending upon the drive
configuration and size
2
2
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
See 10.2 General Technical Data for terminal ratings details.
Terminal Parameter
12, 13
18
19
32
33
27
29
20
39
42
50
53
54
16
Terminal Description
Digital Inputs/Outputs
Default
Setting
Description
-
+24V DC
24V DC supply
voltage. Maximum
output current is
200mA total for all
24V loads. Useable for
digital inputs and
external transducers.
E-01
[8] Start
E-02
[0] No
operation
Digital inputs.
E-05
[0] No
operation
E-06
[0] No
operation
E-03
[0] No
Selectable for either
operation
digital input or
output. Default setting
E-04
[14] JOG
is input.
-
Common for digital
inputs and 0V
potential for 24V
supply.
Analog Inputs/Outputs
-
Common for analog
output
AN-50
Speed 0 -
Programmable analog
High Limit
output. The analog
signal is 0-20mA or
4-20mA at a
maximum of 500Ω
-
+10V DC
10V DC analog supply
voltage. 15mA
maximum commonly
used for potenti-
ometer or thermistor.
AN-1#
Reference
Analog input.
Selectable for voltage
AN-2#
Feedback
or current. Switches
A53 and A54 select
mA or V.
AF-600 FP Operating Instructions
Terminal Parameter
55
61
68 (+)
69 (-)
01, 02, 03
04, 05, 06
Table 2.2 Terminal Description

2.4.5.3 Wiring to Control Terminals

Control terminal connectors can be unplugged from the
drive for ease of installation, as shown in Illustration 2.16.
Illustration 2.16 Unplugging Control Terminals
1.
2.
3.
4.
Terminal Description
Digital Inputs/Outputs
Default
Setting
-
Serial Communication
-
O-3#
O-3#
Relays
E-24 [0]
[0] Alarm
E-24 [1]
[0] Running
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Illustration 2.17.
Insert the bared control wire into the contact.
Remove the screwdriver to fasten the control wire
into the contact.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
Description
Common for analog
input
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
when experiencing
EMC problems.
RS-485 Interface. A
control card switch is
provided for
termination resistance.
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.