Serial Communication - GE AF-600 FP Operating Instructions Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Installation
2
2
Illustration 2.18 Location of Terminals 53 and 54 Switches

2.4.6 Serial Communication

Connect RS-485 serial communication wiring to terminals
(+)68 and (-)69.
Screened serial communication cable is
recommended
See 2.4.2 Earth (Grounding) Requirements for
proper grounding
Illustration 2.19 Serial Communication Wiring Diagram
18
AF-600 FP Operating Instructions
For basic serial communication set-up, select the following
1.
2.
3.
130BT310.10
Protocol type in O-30 Protocol.
Drive address in O-31 Address.
Baud rate in O-32 Drive Port Baud Rate.
Four communication protocols are internal to the
drive. Follow motor manufacturer wiring
requirements.
Drive profile
Modbus RTU
®
Metasys N2
®
Apogee FLN
Functions can be programmed remotely using
the protocol software and RS-485 connection or
in parameter group O-## Options / Comms
Selecting a specific communication protocol
changes various default parameter settings to
match that protocol's specifications along with
making additional protocol-specific parameters
available
Option cards which install into the drive are
available to provide additional communication
protocols. See the option-card documentation for
installation and operation instructions

Advertisement

Table of Contents
loading

Table of Contents