Honeywell Sensepoint XRL Instruction Manual page 58

Fixed gas detector
Hide thumbs Also See for Sensepoint XRL:
Table of Contents

Advertisement

Modbus Register Address Information
40106
Alarm, Fault and Warning State
40107
Monitor State Monitoring
40108
Heart Beat
40109 to 40110
Calibration Due
40111
Measuring Unit
40112 to 40113
Peak Reading
40114
Relay Fitted
40115
BLE Fitted
R/W Type Size Description
R
u8
1
This register contains 4 meaningful bits regarding the presence of alarms
or faults. The bit assignments are as follows: Bit 0: AL1
active Bit 1: AL2 active Bit 4: Warning active Bit 6: Fault Active All others:
For future expansion
R
u8
1
R
u16
1
This Heartbeat is provided to facilitate detection of communications prob-
lems in programming environments where the transport layer communica-
tion error information is unavailable. This increments approximately every
5 seconds. It is the responsibility of the system integrator to notify plant
personnel if a Modbus master fails to communicate with the Sensepoint
XCL/XRL. This register can facilitate this notification
R
f32
2
This indicates the time remaining before the ECC sensor must be calibrated
or replaced. Calibration interval - DaysPassedSinceLastSuccessfulCal
R
u8
1
iMeasurementUnits
R
f32
2
R
u16
1
R
u16
1
Notes
bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
bit 2,3 for future expansion
bit 4 Warning is active
bit 5 Fault is active
bit 6,7 for future expansion
Note: Latching relay setting latches Modbus values in register 40006.
1 : Normal
2 : Warm Up after power on
3 : in Inhibit
12 : Calibration
0x00 : blank (no measurement unit)
0x01 :
0x02 : mA
0x03 : mg/m3
0x04 : g/m3
0x05 :
0x06 : ppm
0x07 : kppm
0x08 : LEL·m
0x09 : A
0x0A : dB
0x0B : dBA
0x0C : ppm·m
Peak Reading
0x00: Relay not fitted, 0x01: Relay fitted
0x00: BLE not fitted, 0x01: BLE fitted