1) Manufacturer information
2) US FCC and Canada IC approval
3) Serial number and part number
4) Electrical rating
5) WEEE marking
6) Canadian flammable gas performance approval
7) Revision check box
8) Country of origin
9) Hazloc marking for class/division and class/zone
10) cULus marking for hazloc approval
11) UL 2075 approval
Specific Condition of Use for CAN/CSA-C22.2 No.60079-0 and
60079-1
Condition d'utilisation spécifique pour CAN / CSA-C22.2 No.60079-0
et 60079-1
• To reduce the risk of ignition of hazardous atmospheres, conduit runs must
have a sealing fitting connected within 50 mm of the enclosure.
Pour réduire le risque d'inflammation des atmosphères dangereuses, les
conduits doivent avoir un joint d'étanchéité raccordé à moins de 50 mm de
l'enceinte.
• Open circuit before removing cover.
Ouvrir le circuit avant de retirer le couvercle.
• Keep cover tight while circuits are alive.
GARDEZ LE COUVERCLE TOUJOURS SI LES CIRCUITS SONT VIVANTS.
• Temperature of the entry point or at branching point is above +70 °C under
rated conditions.
La température du point d'entrée ou au point de ramification est
supérieure à +70 °C dans des conditions nominales.