In Field Device Manager (FDM), the value in the actual field will be displayed as 0. But users can
hover the mouse over the parameters to see the values using Tooltips. It is a known FDM limitation
and future FDM releases will address this issue.
Revision 5.0
Training result
If PILD is enabled:
Success
Failure
If PILD is disabled,
no output.
When PILD is Enabled from Disabled mode,
Current Mode goes to Training Mode.
Training Result will show 'Failure' until Sampling Window
(SWIN) duration has passed. After the SWIN time, Training
Result will show 'Success'.
Note that, the Training Result showing 'Failure' means the
mode switch is still In progress and not yet switched to the
Monitor Mode. Once the mode is in Monitor mode, Training
Result will show 'Success'
Reference of normal PV, which is the median of PV/URL,
and is output from the training mode.
Reference of the noise fluctuation of normal PV, which is
output by training mode.
Current normal PV, which is the median of PV/URL and is
output by monitoring mode.
Fluctuation of the noise fluctuation of normal PV, which is
outputted by monitoring mode.
Value of 1.293723E-06 shows up as 0 in the Edit field
ST 800 Series HART/DE Option User's Manual