Online/Device
Setup/Basic Setup/
Device Information
(Continued ...)
Revision 5.0
Date
Descriptor
Message
Clear Message
Range values
Model Number
Maint Mode
ST 800 Series HART/DE Option User's Manual
Enter a date for user information only.
Enter a descriptor for user information only (up to
16 alphanumeric characters)
Enter a message up to 32 alphanumeric
characters) that will be sent to the Display. The
message will be shown on the Display interspersed
with the configured screens. To stop displaying the
message, select "Clear Display" in the Device
Information menu.
Selecting this option clears the "Message" and it
will no longer be sent to the Display.
Displays all of the range information for the device.
The following limits are read only:
LRL: Lower range limit
URL: Upper range limit
LTL: Lower transducer limit
UTL: Upper Transducer limit
The following may be configured to desired zero
and span ranging for the application:
LRV: Lower Range Value (input which
represents 0% output)
URV: Upper Range Value(input which
represents 100% output)
Valid configurations for LRV and URV range from
LTL to UTL.
Displays the full order model number of the ST 800
Pressure Transmitter
Displays the Maintenance mode set by Experion
PKS.
When a HART device requires maintenance, the
engineer or the operator changes the PV Source
value of the corresponding AI channel to MAN. As
soon as the PV Source value is changed for the
channels connected to the ST 800 transmitters,
Experion communicates the channel mode status
to the corresponding ST 800 transmitters. Upon
receiving this status, if the value is MAN, the
transmitter displays an M and Available for
Maintenance on the local display of the
transmitter. The status display on the transmitter
ensures that the field technician can locate and
perform the maintenance work on the correct
transmitter without impacting the integrated
devices in the process loop. The transmitter
continues to display the Available for
Maintenance status on its local display until the
PV Source status of the corresponding AI channel
is changed to AUTO / SUB or the transmitter is
power cycled.
For more information, refer to the Experion
Knowledge Builder
Page 35