Honeywell ST 800 Series User Manual page 44

Pressure transmitter
Hide thumbs Also See for ST 800 Series:
Table of Contents

Advertisement

Online/Device
Setup/Basic Setup/
Device Information
(Continued ...)
Page 36
Device ID
Final Asmbly num
Universal rev
Fld dev rev
Software rev
Loop mA
PV Units
PV Damping
SV Units
Write Protect
ST 800 Series HART/DE Option User's Manual
Displays the HART unique long address of
the ST 800 Pressure Transmitter
Displays the final assembly number of the ST
800 Pressure Transmitter
Displays the HART Universal Revision of the
ST 800 Pressure Transmitter
Displays Field Device Revision of the ST 800
Pressure Transmitter
Displays the Electronics Board Software
Revision of the ST 800 Pressure Transmitter
Select the Loop Current Mode configuration:
"Enable": enables loop current mode
(analog output will operate as a 4 to
20 mA signal consistent with the
transmitter output)
"Disable": disables loop current mode
(analog output will be fixed at 4 mA)
Select one of the pre-programmed
engineering units. ST 800 Transmitters with
inches of water ranges are factory calibrated
using pressure referenced to 39.2
Pressure readings can be displayed in the
following engineering units:
inH
O
inHg
2
ftH
mmH
O
mmHg
2
bar
mbar
g/cm
2
kg/cm
Pa
kPa
torr
atm
MPa
o
inH
O @ 4
C
mmH
2
inH
Enter a value for damping of the device
output. Entries may be any value from 0.00
to 32.00 seconds.
Select the desired unit for measurement of
the Secondary Variable (Meter Body
Temperature). Selections available are:
o
o
,
F,
R, Kelvin.
Displays the current configuration of the write
protect function. Write Protect is "Enabled" if
either the write protect jumper on the
electronics board is in the "ON" position or
the firmware write protect has been enabled.
o
o
F (4
C).
O
2
psi
2
o
O@4
C
2
o
O @ 60
F
2
o
C
Revision 5.0