CHAPTER 6: ACTUAL VALUES
Base unit
SOURCE THD & HARMONICS
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
VOLTS PER HERTZ
Z
BASE
6.4.9 RxGOOSE analogs
ACTUAL VALUES METERING RxGOOSE Analogs
RxGOOSE
Analogs
The L90 is provided with optional GOOSE communications capability. This feature is specified as a software
option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.
6.4.10 Wattmetric ground fault
ACTUAL VALUES METERING WATTMETRIC GROUND FAULT 1(2)
WATTMETRIC
GROUND FAULT 1
This menu displays the wattmetric zero-sequence directional element operating power values.
6.4.11 Phasor Measurement Unit
ACTUAL VALUES METERING PHASOR MEASURMENT UNIT PMU 1
PMU 1
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Description
BASE = 1%
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
BASE = 1.00 pu
Z
= PhaseVTSecondary / PhaseCTSecondary, where PhaseVTSecondary and
BASE
PhaseCTSecondary are the secondary nominal voltage and the secondary nominal current of the
distance source. In case multiple CT inputs are summed as one source current and mapped as the
distance source, use the PhaseCTSecondary value from the CT with the highest primary nominal
current.
Distance source is specified in setting under SETTINGS GROUPED ELEMENTS SETTING
GROUP 1(6) DISTANCE.
PhaseVTSecondary and PhaseCTSecondary are specified in setting under SETTINGS SYSTEM
SETUP AC INPUTS.
RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
WATT GND FLT 1:
0.000 W
PMU 1 VA:
0.000 V
0.00°
PMU 1 VB:
0.000 V
0.00°
PMU 1 VC:
0.000 V
0.00°
PMU 1 VX:
0.000 V
0.00°
PMU 1 V1:
0.000 V
0.00°
Range: Va or Vab per VT bank connection
Range: Va or Vab per VT bank connection
Range: Va or Vab per VT bank connection
METERING
6
6-25