GE L90 Instruction Manual page 211

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the
displayed on the front panel or the Targets panel of the EnerVista software. The
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1.
Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
Security events
The security events produced when the CyberSentry option is purchased are sent as sytem log (syslog) messages to a
syslog server, if one is configured. The format is as follows.
Security log
Event Number
— Event identification number (index)
Event Number
— UTC date and time
Date & Timestamp
— 255 chars maximum, but in the security log it is truncated to 20 characters
Username
— Device IP address
IP address
— 16 bit unsigned, of type format F617
Role
Enumeration Role
0
None
1
Administrator
2
Supervisor
3
Engineer
4
Operator
5
Factory
— 16 bit unsigned
Activity Value
Enumeration Description
1
Authentication Failed
2
User Lockout
3
FW Upgrade
4
FW Lock
5
Settings Lock
6
Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7
Clear Oscillography command
8
Clear Data Logger command (not applicable to all UR products)
9
Clear Demand Records command (not applicable to all UR products)
10
Clear Energy command (not applicable to all UR products)
11
Clear Unauthorized Access command
12
Clear Teleprotection Counters command (not applicable to all UR products)
13
Clear All Relay Records command
14
Role Log in
15
Role Log off
If "System Integrity Recovery" events are logged during a restart of the unit due to an incorrect shutdown sequence,
upgrade the firmware to version 7.31 or later to correct this issue.
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
button, which resets targets, where targets are errors
RESET
Date &
Username
Timestamp
button has special behavior in that it
RESET
IP address
Role
PRODUCT SETUP
Activity Value
5
5-25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF