Virtual Outputs; Rxgoose Status; Rxgoose Statistics - GE L90 Instruction Manual

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

STATUS
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, 'Cont Op 1' refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.

6.3.7 Virtual outputs

ACTUAL VALUES  STATUS  VIRTUAL OUTPUTS
 VIRTUAL OUTPUTS
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, 'Virt Op 1' refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.

6.3.8 RxGOOSE status

ACTUAL VALUES  STATUS  RxGOOSE STATUS
 RxGOOSE
 STATUS
6
The L90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The
All RxGOOSE Online
Input.

6.3.9 RxGOOSE statistics

ACTUAL VALUES  STATUS  RxGOOSE STATISTICS  RxGOOSE 1(64)
 RxGOOSE 1
The L90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
6-6
Cont Op xx
Off
Virt Op 1
Off
Virt Op 96
Off
All RxGOOSE Online:
Yes
RxGOOSE 1 Status:
Offline
RxGOOSE 64 Status:
Offline
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
RxGOOSE 1
stNum:
RxGOOSE 1
sqNum:
Range: On, Off, VOff, VOn, IOn, IOff
Range: On, Off
Range: On, Off
Range: Yes, No
Range: Online, Offline
Range: Online, Offline
Range: 0 up to 4,294,967,295
0
Range: 0 up to 4,294,967,295
0
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES