SYSTEM SETUP
5.5.6 Disconnect switches
SETTINGS SYSTEM SETUP SWITCHES SWITCH 1(24)
SWITCH 1
5
The disconnect switch control element contains the auxiliary logic for status and serves as the interface for opening and
closing of disconnect switches from SCADA or through the front panel interface. The disconnect switch control element
can be used to create interlocking functionality. For greater security in determination of the switch pole position, both the
89/a and 89/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available
disconnect switches is four per breaker.
To use this element, configure the contact outputs that open and close the disconnect switch to use FlexLogic operands
and
SWITCH 1 OFF CMD
SWITCH 1 FUNCTION
— Assign a user-defined name (up to six characters) to the disconnect switch. This name is used in flash
SWITCH 1 NAME
messages related to disconnect switch 1.
— This setting selects "3-Pole" mode, where disconnect switch poles have a single common auxiliary
SWITCH 1 MODE
switch, or "1-Pole" mode where each disconnect switch pole has its own auxiliary switch.
— This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch 1
SWITCH 1 OPEN
open command.
5-138
SWITCH 1
FUNCTION: Disabled
SWITCH 1 NAME:
SW 1
SWITCH 1 MODE:
3-Pole
SWITCH 1 OPEN:
Off
SWITCH 1 BLK OPEN:
Off
SWITCH 1 CLOSE:
Off
SWITCH 1 BLK CLOSE:
Off
SWTCH 1 ΦA/3P CLSD:
Off
SWTCH 1 ΦA/3P OPND:
Off
SWITCH 1 ΦB CLOSED:
Off
SWITCH 1 ΦB OPENED:
Off
SWITCH 1 ΦC CLOSED:
Off
SWITCH 1 ΦC OPENED:
Off
SWITCH 1 TOPERATE:
70 ms
SWITCH 1 ALARM
DELAY:
SWITCH 1 EVENTS:
Disabled
CMD, and configure the disconnect switch control element's inputs as outlined here.
SWITCH 1 ON
— This setting enables and disables operation of the disconnect switch element.
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 65535 ms in steps of 1
Range: 0.000 to 65.535 s in steps of 0.001
0.000 s
Range: Disabled, Enabled
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS