PRODUCT SETUP
Buffered Report1 BufTm
Range: 0 to 4294967295 in steps of 1
Default: 0 ms
The entered value sets the time interval in milliseconds for the buffering of events for inclusion in a single report.
Buffered Report1 TrgOps
Range: The check box for an individual bit can be enabled or not
Default: All bits enabled / true
The TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are as
follows. Uncheck any trigger conditions that are not needed.
data-change
quality-change
integrity
general interrogation
5
Buffered Report1 IntgPd
Range: 0 to 4294967295 in steps of 1
Default: 0 ms
The entered value sets the period in milliseconds for generating Buffered Report1 integrity reports. An integrity report
includes the values of all members of the referenced data set, whether a change has occurred or not.
Each unbuffered report has the following settings.
Unbuffered Report1 RptID
Range: 0 to 129 VisibleString characters
Default: empty string
The name of the report. The entered value sets the RptID value in Unbuffered Report1 messages, and it can be used by
the client to discriminate Unbuffered Report1 messages from other messages. If the number of characters entered is
zero, the value used for RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/
LLN0$RP$"URCB01".
Unbuffered Report1 Name
Range: 0 up to 32 VisibleString characters
Default: URCB01
The entered value sets the report control block name value for Unbuffered Report1.
Unbuffered Report1 DatSet
Range: None, TT6DataSet1, TT6 DataSet2, ..., TT3DataSet01, TT3DataSet02, ...
Default: None
This setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
5-70
Figure 5-25: Options for buffered report messages
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS