Removing and Replacing Field-Replaceable Units

Removing and Replacing Field-Replaceable Units

Replacing the Air Filter

Note
Step 1
Cisco 10005 ESR Hardware Overview and Maintenance Guide
3-6
This section contains procedures to remove and replace all of the field replaceable
units (FRUs) for the Cisco 10005 ESR.
If the air filter is dirty or clogged, the fan assembly might not be able to provide
sufficient cooling air flow through the chassis, causing the system to overheat. To
prevent an overheating problem, replace the air filter every 6 months. In dirty or
dusty environments, replace the filter more frequently.
If you want to reuse the air filter, use a vacuum cleaner to remove the dust.
The air filter is accessible from the rear of the chassis. It occupies a vertical slot
on the left side of the chassis.
To replace the air filter:
Use a flat blade screwdriver to turn the cam fastener on the air filter cover one half
of a rotation (180 degrees)
Chapter 3
(Figure
3-1).
Maintaining the Cisco 10005 ESR
OL-1102-07