Measuring Resistance Values; Dismantling And Disposal - Honeywell ASC02-01WM Installation And Operating Instructions Manual

Temperature differential controller 2 inputs, 1 output
Table of Contents

Advertisement

Dismantling and disposal

9.2.2.1
32

Measuring resistance values

► Disconnect the corresponding temperature sensor from the
controller.
► Measure the resistance value. The typical resistance values,
depending on the temperature, are listed in the following table.
Please note that small deviations are permissible.
Temperature sensor resistance values
Temperature [°C]
Resistance [Ω]
Temperature [°C]
Resistance [Ω]
Temperature [°C]
Resistance [Ω]
Temperature [°C]
Resistance [Ω]
10 Dismantling and disposal
DANGER
Risk of death by electrocution!
► Remove the controller from the power supply before
dismantling the controller.
► To dismantle the controller, follow the assembly instructions in
the reverse order.
► Dispose of the controller in accordance with the regional
regulations.
–30
–20
–10
882
922
961
30
40
50
1117
1155 1194 1232
90
100
110
1347
1385 1423 1461
150
160
170
1573
1611 1648 1685
ASC02-01WM
0
10
20
1000
1039
1078
60
70
80
1271
1309
120
130
140
1498
1536
180
EN2B-0365GE51 R0710