L90 line current differential system ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 57 of 57)
ADDR
REGISTER NAME
EB58
PMU 1 Voltage Trigger Dropout Time
EB59
PMU 1 Voltage Trigger Block (3 items)
EB5C
PMU 1 Voltage Trigger Target
EB5D
PMU 1 Voltage Trigger Events
Phasor Measurement Unit One-shot Command (Read/Write Setting)
EB82
PMU One-shot Function
EB83
PMU One-shot Sequence Number
EB84
PMU One-shot Time
Phasor Measurement Unit Test Values (Read/Write Setting)
EB86
PMU 1 Test Function
EB87
PMU 1 Phase A Voltage Test Magnitude
EB89
PMU 1 Phase A Voltage Test Angle
EB8A
PMU 1 Phase B Voltage Test Magnitude
EB8C
PMU 1 Phase B Voltage Test Angle
EB8D
PMU 1 Phase C Voltage Test Magnitude
EB8F
PMU 1 Phase C Voltage Test Angle
EB90
PMU 1 Auxiliary Voltage Test Magnitude
EB92
PMU 1 Auxiliary Voltage Test Angle
EB93
PMU 1 Phase A Current Test Magnitude
EB95
PMU 1 Phase A Current Test Angle
EB96
PMU 1 Phase B Current Test Magnitude
EB98
PMU 1 Phase B Current Test Angle
EB99
PMU 1 Phase C Current Test Magnitude
EB9B
PMU 1 Phase C Current Test Angle
EB9C
PMU 1 Ground Current Test Magnitude
EB9E
PMU 1 Ground Current Test Angle
EB9F
PMU 1 Test Frequency
EBA1
PMU 1 Test df/dt
Phasor Measurement Unit Recorder Configuration Counter Command (Read/Write Command)
EBF6
PMU 1 Recorder Clear Configuration Counter
Phasor Measurement Unit Recording Values (Read Only)
EBFA
PMU 1 Available Records
EBFB
PMU 1 Second Per Record
EBFD
PMU 1 Last Cleared Date
Setting file template values (read only)
ED00
FlexLogic™ displays active
ED01
Reserved (6 items)
ED07
Last settings change date
ED09
Template bitmask (750 items)
Phasor Measurement Unit Records (Read Only)
EFFF
PMU Recording Number of Triggers
GE Multilin
RANGE
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 59
0 to 235959
0 to 1
0 to 700
-180 to 180
0 to 700
-180 to 180
0 to 700
-180 to 180
0 to 700
-180 to 180
0 to 9.999
-180 to 180
0 to 9.999
-180 to 180
0 to 9.999
-180 to 180
0 to 9.999
-180 to 180
20 to 70
-10 to 10
0 to 1
0 to 65535
0 to 6553.5
0 to 400000000
0 to 1
---
0 to 4294967295
0 to 65535
0 to 65535
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F001
---
1
F050
---
1
F102
kV
0.01
F003
°
0.05
F002
kV
0.01
F003
°
0.05
F002
kV
0.01
F003
°
0.05
F002
kV
0.01
F003
°
0.05
F002
kA
0.001
F004
°
0.05
F002
kA
0.001
F004
°
0.05
F002
kA
0.001
F003
°
0.05
F002
kA
0.001
F004
°
0.05
F002
Hz
0.001
F003
Hz/s
0.001
F002
---
1
F126
---
1
F001
---
0.1
F001
---
1
F050
---
1
F102
---
---
---
---
1
F050
---
1
F001
samples
1
F001
DEFAULT
100
0
0 (Self-reset)
0 (Disabled)
B
0 (Disabled)
1
0
0 (Disabled)
50000
0
50000
-120
50000
120
50000
0
1000
-10
1000
-130
1000
110
0
0
60000
0
0 (No)
0
0
0
1 (Enabled)
---
0
0
0
B-65