B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 50 of 57)
ADDR
REGISTER NAME
C71C
...Repeated for Contact Output 62
C728
...Repeated for Contact Output 63
C734
...Repeated for Contact Output 64
Reset (Read/Write Setting)
C750
FlexLogic™ operand which initiates a reset
B
Control Pushbuttons (Read/Write Setting) (7 modules)
C760
Control Pushbutton 1 Function
C761
Control Pushbutton 1 Events
C762
...Repeated for Control Pushbutton 2
C764
...Repeated for Control Pushbutton 3
C766
...Repeated for Control Pushbutton 4
C768
...Repeated for Control Pushbutton 5
C76A
...Repeated for Control Pushbutton 6
C76C
...Repeated for Control Pushbutton 7
Clear Records (Read/Write Setting)
C770
Clear Fault Reports operand
C772
Clear Event Records operand
C773
Clear Oscillography operand
C774
Clear Data Logger operand
C775
Clear Breaker 1 Arcing Current operand
C776
Clear Breaker 2 Arcing Current operand
C777
Clear Breaker 3 Arcing Current operand
C778
Clear Breaker 4 Arcing Current operand
C77B
Clear Demand operand
C77C
Clear Channel Status operand
C77D
Clear Energy operand
C77F
Clear Unauthorized Access operand
C782
Reserved (13 items)
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0
Force Contact Input x State (96 items)
C800
Force Contact Output x State (64 items)
Channel Tests (Read/Write)
C840
Local Loopback Function
C841
Local Loopback Channel
C842
Remote Loopback Function
C843
Remote Loopback Channel
C844
Remote Diagnostics Transmit
Direct Input/Output Settings (Read/Write Setting)
C850
Direct Input Default States (8 items)
C858
Direct Input Default States (8 items)
C860
Direct Output x 1 Operand (8 items)
C868
Direct Output x 2 Operand (8 items)
Remote Devices (Read/Write Setting) (16 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID
CB21
Remote Device 1 GOOSE Ethernet APPID
CB22
Remote Device 1 GOOSE Dataset
CB23
Remote Device 1 in PMU Scheme
CB24
...Repeated for Device 2
CB48
...Repeated for Device 3
CB6C
...Repeated for Device 4
CB90
...Repeated for Device 5
CBB4
...Repeated for Device 6
CBD8
...Repeated for Device 7
CBFC
...Repeated for Device 8
B-58
RANGE
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
0 to 2
0 to 3
0 to 1
1 to 2
0 to 1
1 to 2
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
---
0 to 16383
0 to 8
0 to 1
L90 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
---
F001
---
1
F144
---
1
F131
---
1
F126
---
1
F001
---
1
F126
---
1
F001
---
1
F223
---
1
F108
---
1
F108
---
1
F300
---
1
F300
---
---
F209
"Remote Device 1"
---
1
F001
---
1
F184
---
1
F126
DEFAULT
0
0 (Disabled)
0 (Disabled)
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0 (Disabled)
0 (No)
1
0 (No)
1
0 (NO TEST)
0 (Off)
0 (Off)
0
0
0
0 (Fixed)
0 (No)
GE Multilin