1 GETTING STARTED
3.
Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4.
Click on the "Use the following IP address" box.
5.
Enter an IP address with the first three numbers the same as the IP address of the L90 relay and the last number dif-
ferent (in this example, 1.1.1.2).
6.
Enter a subnet mask equal to the one set in the L90 (in this example, 255.0.0.0).
7.
Click OK to save the values.
Before continuing, it will be necessary to test the Ethernet connection.
1.
Open a Windows console window by selecting Start > Run from the Windows Start menu and typing "cmd".
2.
Type the following command:
C:\WINNT>ping 1.1.1.1
3.
If the connection is successful, the system will return four replies as follows:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
4.
Note that the values for
time
If the following sequence of messages appears when entering the
GE Multilin
and
TTL
will vary depending on local network configuration.
L90 Line Current Differential System
1.3 ENERVISTA UR SETUP SOFTWARE
C:\WINNT>ping 1.1.1.1
command:
1
1-11