8 SECURITY
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.
Proper passwords are required to enable each command or setting level access. A command or setting password consists
of 1 to 10 numerical characters and are initially programmed to "0". The following procedure describes how the set the com-
mand or setting password.
1.
Enter the new password in the Enter New Password field.
2.
Re-enter the password in the Confirm New Password field.
3.
Click the Change button. This button will not be active until the new password matches the confirmation password.
4.
If the original password is not "0", then enter the original password in the Enter Password field and click the Send
Password to Device button.
5.
The new password is accepted and a value is assigned to the
If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password
value.
PATH: SETTINGS
PRODUCT SETUP
ACCESS
SUPERVISION
MESSAGE
MESSAGE
GE Multilin
Figure 8–1: REMOTE PASSWORD SETTINGS WINDOW
SECURITY
ACCESS SUPERVISION
ACCESS LEVEL
TIMEOUTS
INVALID ATTEMPTS
BEFORE LOCKOUT: 3
PASSWORD LOCKOUT
DURATION: 5 min
L90 Line Current Differential System
8.1 PASSWORD SECURITY
8.1.4 REMOTE PASSWORDS
item.
ENCRYPTED PASSWORD
8.1.5 ACCESS SUPERVISION
Range: 2 to 5 in steps of 1
Range: 5 to 60 minutes in steps of 1
8
8-3