05.08
Response
Remedy
Program
continuation
© Siemens AG 2008 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 05.2008 Edition
10.2 NCK safety alarms for SINUMERIK 840D sl
– The logical basis address configured in HW config and that ad-
dressed via MD $MA_SAFE_CTRLOUT_NR,
$MN_SAFE_DRIVE_LOGIC_ADDRESS do not match or the slot
that is addressed has the incorrect length.
– Cam position $MA_SAFE_CAM_POS_PLUS[n] or
$MA_SAFE_CAM_POS_MINUS[n] has been parameterized too
close to the modulo limit.
– "Safe cams" have been enabled in $MA_SAFE_FUNC-
TION_ENABLE in bits 8 to 15, while the "Safe cam track" function
was enabled at the same time in $MA_SAFE_CAM_ENABLE.
– The assignment of the logical I/O address of this SI telegram of this
drive via $MA_SAFE_DRIVE_LOGIC_ADDRESS does not match
the configured telegram (Step 7).
– Minus cam position $MA_SAFE_CAM_POS_MINUS[n] is greater
than the plus cam position $MA_SAFE_CAM_POS_PLUS[n]. This
is not permitted for the "safe cam track" function.
– The distance between 2 cams on a cam track
($MA_SAFE_CAM_POS_MINUS[n] and
$MA_SAFE_CAM_POS_PLUS[n]) is too short.
– The cam length, i.e. the distance between the plus cam position
($MA_SAFE_CAM_POS_PLUS[n]) and minus cam position
($MA_SAFE_CAM_POS_MINUS[n]) is too short.
– For at least 2 cams enabled in $MA_SAFE_CAM_ENABLE,
identical values have been entered into $MA_SAFE_CAM_TRACK_
ASSIGN[n].
– The value parameterized in $MA_SAFE_CAM_TRACK_ASSIGN[n]
for a cam enabled in $MA_SAFE_CAM_ENABLE is invalid.
– The cam modulo functionality in $MA_SAFE_MODULO_RANGE is
selected but is presently still not supported for the "safe cam track"
function.
Mode group not ready
Channel not ready
NC start inhibit in this channel
Interface signals are set
Alarm display
NC stop for alarm
Check and modify the MD named in the alarm text. Have the checksum
re–calculated. Safety functions should be subject to a new acceptance
test.
Power–down the control and power–up again