Safety Functions Integrated in the System/Drive
6.5 Safely reduced speed (SG)
6.5.2
Selecting/deselecting safely reduced speed
Selecting SG
The following SGEs are used to select SG:
Table 6-11
SBH/SG
deselection
= 1
= 0
= 0
Note: x –> Any signal state
Note
The actual status of the function is displayed using the SGA "SBH/SG active" and
SGA "SBH active".
Before activating the SG function it must be ensured that the speed of the
axis/spindle is lower than the selected speed limit value. If it is higher, an alarm is
generated that causes the drive to be shut down.
The SGEs and SGAs are described in Chapter 7.1 "Safety–related input/output
signals (SGE/SGA)".
Selecting speed limit values
The maximum permissible speed of an axis/spindle in the setting–up mode is de-
fined for individual machine types in the C Standards (product standards). The ma-
chine manufacturer is responsible for ensuring that the correct speed limit value is
selected depending on the operating mode and the application.
The required speed limit is selected as follows by combining the following SGEs:
6-150
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 05.2008 Edition
Selecting/deselecting SG
SGE
SBH
Description
deselection
x
SBH and SG are deselected
= 0
SBH is selected
(see Chapter 6.2, "Safe operating stop (SBH)"
= 1
SG is selected
© Siemens AG 2008 All Rights Reserved