Network Port And Communication Protocols; Direct Communication - GE Reason RT430 Technical Manual

A clock referenced to gps and glonass satellites
Hide thumbs Also See for Reason RT430:
Table of Contents

Advertisement

GPS Grandmaster Clock
Factory's default port to connect to the Gateway is the Ethernet 1. The factory default setting of Gateway and
DNS Server are:
The E
parameters can be configured through a Web Interface. For details of E
THERNET
configuration, see
Chapter
3.3

Network port and communication protocols

To ensure free access to communication via Ethernet, the following ports and protocols should be enabled:
TABLE 28: Communication port and protococols.
Port
Protocol
80
TCP/IP
123
UDP
319
UDP
320
UDP
443
HTTPS
3.4

Direct Communication

46
TABLE 26: Ethernet 2 port are listed below
IP Address
Netmask
Broadcast
TABLE 27: Gateway and DNS Server.
Gateway (E
1)
THERNET
Server DNS
4.
Remote access via Web
SNTP Time synchronism
Sending event messages PTP to sychronize
Sending general messages via PTP to sychronize
Establishing a safe connection via Web interface
192.168.1.199
255.255.255.0
192.168.1.255
192.168.0.254
192.168.0.254
Use
ports
THERNET
RT430-TM-EN-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents