Slip Compensation Frequency - Panasonic VF200 Instruction Manual

Table of Contents

Advertisement

Appendix Function Parameter List
P134

Slip Compensation Frequency

During vector control or when slip compensation is performed through V/F
control, slip compensation frequency can be set.
Setting value (Hz)
-5.00 to 5.00 (increment = 0.01)
Slip compensation frequency is set by converting slip (at 60 Hz) to frequency
value.
Please make settings according to the following method.
・If the setting value is relatively high, RPM of motor may be higher than the
target value.
・When the setting value is relatively low, RPM of motor may be lower than the
target value.
・Automatic tuning sometimes cannot be performed when the inverter is
affected by power supply environment and connected with special-purpose
motor etc. In this case, please make manual settings according to relevant
methods.
"P134: Slip Compensation Frequency" can also be tuned automatically with
"P132: Motor Constant Measuring Function".
Related parameters: P129 to P133, P156, P158 to P161
253

Hide quick links:

Advertisement

Table of Contents
loading