Summer Switch-Off (Heating Limit) - Honeywell SDC Operating Instructions Manual

Heating and district heating controller
Hide thumbs Also See for SDC:
Table of Contents

Advertisement

Operation
4.2.3.3.3 Separate Operating Mode
OP. MODE
MC 2
æ ç è é ê ë ì í
AUTOMATIC
MC 2
æ ç è é ê ë ì í

4.2.3.4 Summer Switch-off (heating limit)

rices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub.co.uk - info@mytu
Factory setting
Setting range
Function
Function
Alternatively, the value can be acquired by automatic
exit after approx. 60 s.
16 °C
5...30 °C
In control mode 2 the selected program applies only for
the heating circuit specified previously.
Hence, each heating circuit can be assigned its own
operating mode.
Setting:
Press the "operating mode" key ¢.
Select the desired heating circuit, i.e. HC, MC-1 or
MC-2, with the rotary pushbutton î. .
Confirm the circuit by pressing the pushbutton î. .
Set the flashing operating mode by turning to the
desired value.
Confirm the set value by pressing the "operating
mode" ¢ or the rotary pushbutton î.
In case of short-term operating modes (Holiday,
Absence, Party) set the desired target value by
turning the rotary pushbutton î and confirm the set
value as described above.
Alternatively, the value can be acquired by automatic
exit after the set INFO-TIME (see "System
Information).
This parameter determines the end of the heating
season based on the outside temperature according to
the following criteria:
Rapid increase of the outside temperature
As long as the mean outside temperature is below the
37
SDC / DHC 43
EN2H-0220 GE51 R1005