Manual Mode" / "Emission Measurement" Key - Honeywell SDC Operating Instructions Manual

Heating and district heating controller
Hide thumbs Also See for SDC:
Table of Contents

Advertisement

SDC / DHC 43
Automatic Exit
INFO-TIME
æ ç è é ê ë ì í
Setting range
Factory setting

4.1.2.8 "Manual Mode" / "Emission Measurement" Key

4.1.2.8.1 "Manual Mode"
MANUALMODE
o
C
38. 0
æ ç è é ê ë ì í
EN2H-0220 GE51 R1005
rices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub.co.uk - info@mytu
Set Time for
If the "information key" ¤ is pressed for approx. 3 s
upon accessing the information
level, the INFO-TIME parameter appears.
This parameter determines the time for the automatic
return to the basic display.
2. 0
min
OFF, 1...60 min
OFF
1...60 min
OFF
If the "manual mode" / "emission measurement" key is
pressed for more than 5 s while the basic display is
visualized, the controller is switched to manual mode. In
this operating mode the heat generator temperature is
set manually with the rotary pushbutton î according to
the desired setpoint. All the pumps are active, while the
available mixing valves are de-energized and can be
actuated by hand.
c
The heat generator setpoint can be set from 5 to 90 °C
o
40. 0
and it flashes on the left hand of the display, while the
actual heat generator temperature is visualized statically
on the right hand of the display.
No exit, the last information displayed
remains constantly until the next setting on
the display.
Automatic exit from the information level
after the specified time, settable in 0.5
minute steps.
22
Operation