System mode functions

NOTE: Default system mode of operation is dependent on sequence of operation selected
• Default mode is bold, as shown in Table 6, when the sequence of operation parameter is changed.
• The available mode can only be changed through the network since there is no local mode access.
Sequence selected
0 = Cooling only
1 = Heating only
2 = Cooling with reheat
3 = Heating with reheat
4 = Cooling and Heating (2 modulating outputs)
5 = Cooling/Heating (2 modulating outputs) with reheat

INSTALLER CONFIGURATION PARAMETER MENU

This section describes the parameters available for TB7200 Series thermostat configuration. The TB7200 Series can
be programmed at the thermostat or through WEBStation-AX, with the following exception: Wireless models must have
the Com Addr, PAN ID, and Channel set at the thermostat before adding to the wireless network or doing any
programming in WEBStation-AX.
To program the thermostat through WEBStation-AX, refer to the BACnet Integration Reference Guide for BACnet
models (Form No. 63-4524) or the Wireless Installation and Integration Reference Guide for TB7200, TB7300, TB7600
Thermostats (Form No. 63-4522) for wireless models.
Local configuration:
1. To enter configuration, press and hold the Override button for 8 seconds
2. If a password lockout is active, "Password" is prompted. Enter password value using the "up" and "down" arrows
and press the Override button again to gain access to all configuration properties of the thermostat. A wrong
password entered will prevent local access to the configuration menu.
3. Press the Override button repetitively to scroll between all the available parameters
4. Use the up and down key to change the parameter to the desired value.
5. To acknowledge and save the new value, press the Override button again.
6. The next listed parameter is now displayed.
Press and hold for 8 seconds to enter the configuration mode.
Override
Pressing repetitively will scroll all available parameters one by one
Down
Adjust parameter value down
Up
Adjust parameter value up
TB7200 SERIES COMMUNICATING ZONE THERMOSTATS
Table 6. System mode functions
Off - Cool
Off - Heat
Off – Auto – Heat – Cool
Off - Heat
Off – Auto – Heat – Cool
Off – Auto – Heat – Cool
Table 7. Configuration interface
11
Mode Menu
62-2019—05

Advertisement