TB7200 SERIES COMMUNICATING ZONE THERMOSTATS
Alarms
• If alarms are detected, they will automatically be displayed at the end of the status display scroll.
• During an alarm message display, the back lit screen will light up at the same time as the message and shut off
during the rest of the status display.
• Two alarms maximum can appear at any given time. The priority for the alarms is as follows:
Indicates that there is a service alarm as per one of the programmable binary input (BI2)
Service
Indicates that the filters are dirty as per one of the programmable binary input (BI2)
Filter
Window
Indicates that the outside window or door is opened and that the thermostat has cancelled any cooling or
heating action (BI1)
STATUS LED'S.
Two status LED's on the thermostat cover are used to indicate a call for
heat or a call for cooling as shown in Fig. 9.
Zoning models
• When heating and reheat is ON, the HEAT LED will illuminate.
• When cooling is ON, the COOL LED will illuminate.

User Control Options

Unoccupied Mode Override
An Override can be made during an unoccupied period. If the Override
option is enabled in the Lockout parameter, pressing the middle override
button will resume occupied setpoints for a time specified by parameter
TOccTime.
An Override can be made during an Unoccupied period. If the Override option is enabled in the Lockout
parameter pressing the override key will resume occupied setpoints for a time specified by parameter
Override
ToccTime
Adjust the setpoints down
• In cooling mode only the cooling setpoint displayed,
Down
• In heating mode only the heating setpoint displayed
• In auto mode (see below)
Adjust the setpoints up
• In cooling mode only the cooling setpoint displayed,
Up
• In heating mode only the heating setpoint displayed
• In auto mode (see below)
• Any setpoint change can be permanent or temporary based on parameter Set Type (setpoint type)
• Any setpoint written through the network, will be permanent and cancel any active temporary setpoints
• Lockouts of access to certain functions is made with the parameter (Lockout)
Cooling
Heating
mode
mode
Cool XX.X
Heat XX.X
°F or°C
°F or°C
Unoccupied setpoints adjustments
Unoccupied setpoints cannot be set or changed by the user in the display status. Changes to unoccupied setpoints are
done using the parameters Unocc HT and Unocc CL or through the WEBStation-AX.
62-2019—05
Table 4. Keypad interface
Table 5. Occupied setpoint adjustments
• Setpoint presented to user is the setpoint from the last action taken by
the thermostat or the one currently in use.
• Both heating and cooling setpoint are changed simultaneously while
Off mode
respecting the minimum configured deadband
No access to
Cool XX.X°F or°C and Heat XX.X°F or°C
setpoint
Both heating and cooling setpoints are change simultaneously
OVERRIDE
Fig. 9. Zoning model thermostat
Auto Mode
10