Specifications; Operating Conditions; Storage Conditions - Honeywell TB7200 Series Installation Instructions Manual

Table of Contents

Advertisement

TB7200 SERIES COMMUNICATING ZONE THERMOSTATS

SPECIFICATIONS

Network Protocol: Models available in BACnet MS/TP or ZigBee wireless mesh
WEBs-AX Controllers: Compatible with WEB-2xx, WEB-6xx, and WEB-7xx
Platform:
WEB-2xx and WEB-6xx - WEBStation-AX 3.0 or later
WEB-7xx - WEBStation-AX 3.5 or later
Thermostat power requirements: 19-30 Vac 50 or 60 Hz; 2 VA Class 2

Operating conditions:

32 F to 122 F (0 C to 50 C)
0% to 95% R.H. non-condensing

Storage conditions:

-22 F to 122 F (-30 C to 50 C)
0% to 95% R.H. non-condensing
Temperature sensor: 10 K NTC thermistor on board
Temperate sensor resolution: ± 0.2 F (± 0.1 C)
Temperature control accuracy: ± 0.9 F (± 0.5 C) @ 70 F (21 C) typical calibrated
Remote Sensor Input: 10K NTC
Occ. Stand-By and Unocc cooling setpoint range: 54 to 100 F (12.0 to 37.5 C)
Occ. Stand-By and Unocc heating setpoint range: 40 F to 90 F (4.5 C to 32 C)
Room and outdoor air temperature display range -40 F to 122 F (-40 C to 50 C)
Proportional band for room temperature control: Cooling and Heating: 3.2 F (1.8 C)
Binary inputs: Dry contact across terminal BI1, BI2 and UI3 to Scom
Contact output rating:
Triac output: 30 Vac, 1 Amp. Maximum, 3 Amp in-rush
Analog: 0 to 10 Vdc into 2KΩ resistance min.
Wire gauge 18 gauge maximum, 22 gauge recommended
Dimensions: See Fig. 10
Approximate shipping weight: 0.75 lb (0.34 kg)
Agency Approvals all models:
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
C-Tick: EN55022:2006, IEC 61326-1:2005.
62-2019—05
OVERRIDE
3-2/5 (86)
Fig. 10. Thermostat dimensions in inches (mm)
5
(125)
1-3/20 (29)
M16970
18

Advertisement

Table of Contents
loading