Honeywell TB7200 Series Installation Instructions Manual page 17

Table of Contents

Advertisement

Configuration
parameters
Auxiliary contact function and
Aux cont
configuration
Default value = 0 Not Used
Floating actuator timing
FL time
Default value = 1.5 minutes
cph
On/Off devices cycles per hour
Default value = 4 cph
Reverse acting or Direct acting
RA/DA
signal for analog output signals
Default value = DA signal
Reheat
Sets the time base for the
reheat output if used
Default value = 0= 15 minute
UI3 dis
Display supply or changeover
temperature
Table 8. Configuration Parameters (Continued)
Default value
TB7200 SERIES COMMUNICATING ZONE THERMOSTATS
Significance and adjustments
0 Aux contact function used for reheat.
IF SEQUENCE IS SET TO REHEAT THROUGH NETWORK OR
LOCAL, Ignore this parameter.
The output will directly follow the occupancy of the thermostat
1 Auxiliary NO, Occ or St-By = Contact Closed/Unoccupied =
Contact Opened
2 Auxiliary NC, Occ or St-By = Contact Opened/Unoccupied =
Contact Closed
Output to follow directly main occupancy and Fan on command
Typically used for 2 position fresh air damper applications.
3 Auxiliary NO, Occ or St-By and Fan On = Contact Closed/
Unoccupied and Fan On or Off = Contact Opened
4 Auxiliary NC, Occ or St-By and Fan On = Contact Opened/
Unoccupied and Fan On or Off = Contact Closed
Output to follow secondary network occupancy command
5 Auxiliary on/off control through auxiliary network command. The
output can be commanded through the network for any required
auxiliary functions through a separate and dedicated network
variable.
TB7200C5x14(x) models only
Maximum stroke time of floating valve actuator. 0.5 to 9.0 in 0.5
minutes increment
TB7200C5x14(x) models only
Will set the maximum number cycles per hour under normal control
operation. It represents the maximum number of cycles that the
equipment will turn ON and OFF in one hour.
Note that a higher cph will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
3, 4, 5, 6,7 and 8 cph
TB72xxF5x14(x) models only
Changes the action of the analog outputs on the analog models.
DA = Direct acting - 0 to 100 % = 0 to 10 Vdc
RA = Reverse acting - 0 to 10 % - 10 to 0 Vdc
Sets the reheat output time base
Valid only if reheat sequences are enabled
0 = 15 minutes
1 = 10 seconds for Solid state relays
Used as diagnostic/service help to troubleshoot and diagnose sensor
operation
Only when UI 3 is configured as an analog input (SS or COS)
17
62-2019—05