6.8.4.3

PROFIenergy - properties of the drive system

SINAMICS drive system devices meet the following requirements:
● The devices are certified for PROFIenergy.
● The devices support PROFIenergy function unit, Class 3.
● The devices support PROFIenergy energy-saving mode 2.
6.8.4.4
PROFIenergy commands
Principle of operation
At the start and end of pauses, the plant operator activates or deactivates the pause function
of the plant after which the IO controller sends the PROFIenergy "START_Pause" /
"END_Pause" command to the PROFINET devices. The device then interprets the content of
the PROFIenergy command and switches off or on again.
Further PROFIenergy functions can be used to fetch device information during the pauses.
The user can use them to transfer the "START_Pause" / "END_Pause" command in time.
PROFIenergy control commands
Control commands
START_Pause
START_Pause_with_time_response Switches from the operating state to the energy-saving mode
END_Pause
PROFIenergy query commands
Query commands
List_Energy_Saving_Modes
Get_Mode
PEM_Status
PEM_Status_with_CTTO
PE_Identify
Query_Version
Get_Measurement_List
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
6.8 Communication via PROFINET IO
Description
Switches from the operating state to the energy-saving mode
depending on the pause duration.
Switches from the energy-saving mode to the operating state
depending on the pause duration.
and also specifies the transition times in the command re-
sponse.
Switches from the energy-saving mode to the operating state.
Cancels a switch from the operating state to the energy-saving
mode.
Description
Determines all supported energy-saving modes.
Determines the energy-saving mode.
Determines the current PROFIenergy status.
Determines the current PROFIenergy status, such as the PEM
status and together with the regular transition time to the oper-
ating state.
Determines the supported PROFIenergy commands.
Shows the implemented PROFIenergy profile.
This command returns the measured value IDs that can be
accessed using the "Get_Measurement_Values" command.
Operation
265