Siemens SINAMICS G130 Operating Instructions Manual page 560

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Technical specifications
12.2 General specifications
Table 12- 5
Derating factor of the output current as a function of the pulse frequency for devices with a rated pulse fre-
quency of 1.25 kHz
Article no.
Type rating
6SL3310-...
[kW]
1GE36-1AAx
315
1GE37-5AAx
400
1GE38-4AAx
450
1GE41-0AAx
560
1GF31-8AAx
110
1GF32-2AAx
132
1GF32-6AAx
160
1GF33-3AAx
200
1GF34-1AAx
250
1GF34-7AAx
315
1GF35-8AAx
400
1GF37-4AAx
500
1GF38-1AAx
560
1GH28-5AAx
75
1GH31-0AAx
90
1GH31-2AAx
110
1GH31-5AAx
132
1GH31-8AAx
160
1GH32-2AAx
200
1GH32-6AAx
250
1GH33-3AAx
315
1GH34-1AAx
400
1GH34-7AAx
450
1GH35-8AAx
560
1GH37-4AAx
710
1GH38-1AAx
800
Note
Derating factors for pulse frequencies in the range between two fixed values
For pulse frequencies in the range between the specified fixed values, the relevant derating
factors can be determined by linear interpolation.
560
Output current
at 1.25 kHz
[A]
2 kHz
Supply voltage 3-phase 380 VAC ... 480 VAC
605
83%
745
83%
840
87%
985
92%
Supply voltage 3-phase 500 VAC ... 600 VAC
175
92%
215
92%
260
92%
330
89%
410
89%
465
92%
575
91%
735
87%
810
83%
Supply voltage 3 AC 660 ... 690 V
85
93%
100
92%
120
92%
150
90%
175
92%
215
92%
260
92%
330
89%
410
89%
465
92%
575
91%
735
87%
810
83%
Derating factor at the pulse frequency
2.5 kHz
4 kHz
72%
64%
72%
64%
79%
64%
87%
70%
87%
70%
87%
70%
88%
71%
82%
65%
82%
65%
87%
67%
85%
64%
79%
64%
72%
61%
89%
71%
88%
71%
88%
71%
84%
66%
87%
70%
87%
70%
88%
71%
82%
65%
82%
65%
87%
67%
85%
64%
79%
64%
72%
61%
Operating Instructions, 07/2016, A5E00331449A
5 kHz
7.5 kHz
60%
40%
60%
40%
55%
40%
60%
50%
60%
40%
60%
40%
60%
40%
55%
40%
55%
35%
55%
35%
50%
35%
55%
35%
55%
35%
60%
40%
60%
40%
60%
40%
55%
35%
60%
40%
60%
40%
60%
40%
55%
40%
55%
35%
55%
35%
50%
35%
55%
35%
55%
35%
Inverter chassis units