Commissioning

5.6 Status after commissioning

5.6
Status after commissioning
LOCAL mode (control via operator panel)
● You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
● Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
● You can specify the setpoint using the "increase" and "decrease" keys or by entering the
appropriate numbers using the numeric keypad.
Analog outputs (for version with TM31)
● The actual speed (r0063) is output as a voltage output in the range 0 to 10 V at analog
output 0 (X522:1, 2).
10 V is equal to the maximum speed in p1082.
● The actual current value (r0068) is output as a voltage output in the range 0 to 10 V at
analog output 1 (X522:4, 5).
10 V corresponds to the current limit (p0640), which is set to 1.5 x the rated motor current
(p0305).
Digital outputs (for version with TM31)
● The "enable pulses" signal is output at digital output 0 (X542:2 and 3).
● The "no fault active" signal is output at digital output 1 (X542:5 and 6) (protection against
wire breakage).
● The "ready to start" signal is output at digital output 8 (X541:2).