Conventional Fire Panel
5
3
1
1
The procedure for OC/Relay 2 to 8 is the same.
4.6
Displaying the Configuration
In the View Config menu, you can display the programming of
the fire panel.
6
i
RESET
Bosch Sicherheitssysteme GmbH
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 3.
This takes you to the OC/Relay Ext submenu.
Press zone key 1 to choose Open Collector 1.
Use the zone keys to make the corresponding
8
setting.
...
–
1=Zone = Alarm (default setting)
–
2 Zone Normal
–
3 Sum Alarm
–
4 Sum PreAlarm
–
5 Sum Fault
–
6 Sum Disable
–
7 Sum Test
–
8 Not Used
Press zone key 6.
This takes you to the View Config menu.
Use arrow keys to scroll more quickly through the
displayed programming.
Hold the arrow key down to scroll through the menu
in increments of 10 steps.
To exit the display, press the ESC key.
System Configuration | en
2014.06 | 7.0 | F.01U.172.980
53