Eol Elements; Resetting Zones - Bosch FPC-500-2 Installation Manual

Conventional fire panel
Hide thumbs Also See for FPC-500-2:
Table of Contents

Advertisement

Conventional Fire Panel
4.1.3

EOL Elements

You can use EOL Devices to specify whether you want to use
resistors or EOL modules for zone termination.
1
3
1
1 2 3 4 5 6 7 8
CS TH: mA
If you select With 4W Module, you must specify the threshold
for the creeping short-circuit.
You can calculate this using the battery calculator included on
the CD.
4.1.4

Resetting Zones

In this menu, you can specify the delay times for resetting
zones. You can specify how long the zones can be disconnected
from the power and how long the stabilization time of the
detector should last. This setting is used for the zone test,
restarting the fire panel and intermediate alarm storage.
Bosch Sicherheitssysteme GmbH
Press zone key 1. This takes you to the System
Config menu.
Press zone key 3.
This takes you to the EOL Devices submenu.
Press zone keys 1 to 3:
3
1=Resistor (default setting, not EN 54‑13
...
compliant)
2 Only 2W Module
3 With 4W Module
System Configuration | en
2014.06 | 7.0 | F.01U.172.980
35