Delay For Mains Fault; Zone Configuration - Bosch FPC-500-2 Installation Manual

Conventional fire panel
Hide thumbs Also See for FPC-500-2:
Table of Contents

Advertisement

44
en | System Configuration
Display total delay
2
3
2
The total delay is displayed.
4.2.4

Delay for Mains Fault

The Power Fault menu option enables you to specify the delay
after which an error message indicating a power supply failure
(mains or battery) is to be displayed. If the fault is resolved
before the time set here, it is no longer displayed.
2
4
1
4.3

Zone Configuration

In the Zone Config menu, you can program the individual zones
of the fire panel. Depending on the panel, you can set 2, 4 or 8
zones. The following zone types are available:
2014.06 | 7.0 | F.01U.172.980
Press zone key 2. This takes you to the Delay Config
menu.
Press zone key 3.
This takes you to the Int Alarm Stor submenu.
Press zone key 2.
This takes you to the Total Delay submenu.
Press zone key 2. This takes you to the Delay Config
menu.
Press zone key 4.
This takes you to the Power Fault submenu.
Use the zone keys to set the respective delay.
5
1=No Delay (default setting)
...
2 1 min
3 5 min
4 10 min
5 15 min
Conventional Fire Panel
Bosch Sicherheitssysteme GmbH