Advertisement

Quick Links

Analog Addressable Fire Panels
FPA-1000
en
Release Notes

Advertisement

loading

Summary of Contents for Bosch FPA-1000

  • Page 1 Analog Addressable Fire Panels FPA-1000 Release Notes...
  • Page 3 Analog Addressable Fire Panels Table of Contents | en Table of Contents General Notes Short Description Version Naming of the FPA-1000 Software Release Notes for Version 2.01 New Features in Version 2.01 Issues Fixed in Version 2.01 Known Issues in Version 2.01 Release Notes for Version 1.14...
  • Page 4: Table Of Contents

    10.3 Known Issues in Version 1.01 Release Notes for Version 1.00 11.1 New Features in Version 1.00 11.2 Issues Fixed in Version 1.00 11.3 Known Issues with Version 1.00 F.01U.075.638 | 08 | 2012.08 Release Notes Bosch Security Systems, Inc.
  • Page 5 The FPA-1000-V2 control panels can be interconnected for peer-to-peer communication using Networking Cards. This allows up to eight FPA-1000-V2 control panels to act as a single group in a network in which all interconnected control panels act as one panel.
  • Page 6: Release Notes For Version 2.01

    | Release Notes for Version 2.01 Analog Addressable Fire Panels Release Notes for Version 2.01 New Features in Version 2.01 The following features apply to both the FPA-1000-UL and the FPA-1000-V2: – New devices: Supports the following new Bosch SLC Devices: –...
  • Page 7: Known Issues In Version

    Counting zone: Counting Zone does not count properly if the Global Delay Mode is configured as Sandwich/Dual Zone and no floors are enabled for Sandwich or no dual zone dependancies are set Bosch Security Systems, Inc. Release Notes F.01U.075.638 | 08 | 2012.08...
  • Page 8 Analog Addressable Fire Panels – Shorted Option Bus Terminals issue: If option bus ternimal B (gnd) and terminal G (tx) are shorted, a transistor may break requiring replacement of the panel. F.01U.075.638 | 08 | 2012.08 Release Notes Bosch Security Systems, Inc.
  • Page 9: Release Notes For Version 1.14

    PAS delay issue: PAS does not delay the off premise reporting. Activation of the event starts an immediate report. Release Notes for Version 1.13 New Features in Version 1.13 No new features introduced in this version. Bosch Security Systems, Inc. Release Notes F.01U.075.638 | 08 | 2012.08...
  • Page 10 Issues Fixed in Version 1.13 – Alarm Verification Issue: The issue where the version 1.10, 1.11 or 1.12 FPA-1000 FACP may fail to recognize a verified smoke alarm when the Alarm Verification feature is turned on has been corrected for analog SLC detectors.
  • Page 11 For the FPE-1000-SLC V1.25 or higher, the maximum SLC current is increased to allow more devices being connected to one SLC – FLM-325-B6S: Programming option for activation by host detector Bosch Security Systems, Inc. Release Notes F.01U.075.638 | 08 | 2012.08...
  • Page 12 | Release Notes for Version 1.10 Analog Addressable Fire Panels – NAC appliances (refer to FPA-1000-UL NAC Compatibility List, P/N F.01U.075.636): – New Wheelock and System Sensor devices have been added to the compatible devices’ list – Gentex devices registered –...
  • Page 13 – Page 136: The description about the item "Compare Configuration" does not exactly match the software functionality. In fact, it should say, "You can compare either two different FPA-1000-UL configuration? files or preview saved/unimplemented changes".? – Real-time event printing features including programmable delay: This feature is described in the IOG and Online Help, but is not yet available on MMI and Web page.
  • Page 14 FAA-325-B6S menu for the detector: The menu item Edit Sounder Base for detectors is removed. The menu was intended as a shortcut from Add A Device or Edit A Device to Edit Sounder Base when programming SLC devices. The FPA-1000-UL Installation and Operation Guide will be updated accordingly with Version 3.0. –...
  • Page 15 Confirmation for remote programming access: As soon as the option Confirm At Panel is enabled from the menu, web programming is allowed for 25 minutes. Remote programming is disabled 25 minutes later. Bosch Security Systems, Inc. Release Notes F.01U.075.638 | 08 | 2012.08...
  • Page 16: Known Issues With Version