Conventional Fire Panel
4.1.5
Aux Power
The With Zone setting relates to the last zone of the fire panel.
If the last zone is reset after a pre-alarm or alarm, the AUX
power supply is reset simultaneously.
The With Panel setting also resets the power supply each time
the fire panel is reset.
If you select Never, the auxiliary power supply is never reset.
1
5
1
4.1.6
Faults
The Faults setting specifies whether faults on the fire panel are
to be displayed until the fire panel is manually reset.
Notice!
This setting does not apply to system faults.
System faults can only be reset manually.
Bosch Sicherheitssysteme GmbH
Press zone key 1. This takes you to the System
Config menu.
Press zone key 5.
This takes you to the Aux Power submenu.
Press zone keys 1 to 3.
3
–
1=With Zone (default setting)
...
–
2 With Panel
–
3 Never
System Configuration | en
2014.06 | 7.0 | F.01U.172.980
37