Sensors Activating Service Signal (H4/U5) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
27.5
Action
"Menu"
Scroll to menu H4.
"↵ "
Scroll to menu U5.
"↵ "
"ESC"
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Sensors activating SERVICE signal (H4/U5)

When SERVICE signal is generated in the system, following symbol
is shown in the display's symbol area:
Regarding the SERVICE signal levels, see Planning Instructions,
chapter "SERVICE signal".
Menu H4/U5 is a dynamic list of the sensor(s) activating SERVICE
signal.
NOTE! SERVICE signal is only information that the sensor has to be
replaced with a new/clean sensor soon. The SERVICE signal has to
be acknowledged, see chapter "Acknowledge SERVICE signal
(H8/S3)", page 132.
Text in display
H4 Present system status
U1 Disablement
U2 Disablement by time channel
U3 Open doors
U4 Sensor values
U5 Sensors activating SERVICE signal
U6 Event log
U7 Information
U5 Sensors activating SERVICE signal
Sensor : ZZZ-AA (technical address xxxxxx) needs
service
....
....
Escape
menu
Print
U5 Sensors activating SERVICE signal
NOTE!
During printing "Print" will be replaced with "Abort
printing".
Sensor 1 of 1
111
Comments
According to chapter
"Access", see page 85.
A dynamic list in which
you can scroll with "▼"
or "▲".
If printer is mounted the
soft key "Print" will be
visible, else not. Press
"Print" for a print-out of
all items in the list.
If there are no sensors
having generated
SERVICE signal when
"
" is pressed, the list
view will not open.
Scroll to another menu or
press "ESC".