Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Maintenance (H8)

Access code for service / maintenance

Access code to level 3A is required for menu H8.

Disconnect loop (H8/S1)

Before physical connection / disconnection of loop units, etc. the loop
(or zone line) shall be disconnected (disabled), i.e. there will be no
voltage on the "loop", to avoid damage on the units and the c.i.e.
Zone line input requires an 8 zones expansion board 4580 in the
control unit or an Addressable multipurpose I/O unit 3361 connected
on a COM loop.
Text in display
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
Disconnect type:
COM-loop
Zone line input
Addr zone interface
Disconnect COM-loop
COM-loop: 0, control unit: 00
Disconnect zone line input
Zone line input: 0, exp board: 0, control unit: 00
Disconnect addressable zone interface
Input technical number: 000000
Disconnect type:
COM-loop
Zone line input
Addr zone interface
S1 Disconnect loop / zone line input
129
Comments
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
"▲" or "▼" to
Use
select a type and press
"↵ ".
Write the required data and
press "↲ ".
Continue to disconnect or
press "ESC" to menu S1.
LED Fault / Disablements
"General disablements"
(L10) will light up.