Re-Enable Zone (H2/B4) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
25.4
Action
"Menu"
Scroll to menu H2.
"↵ "
Scroll to menu B4.
"↵ "
"↵ "
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Re-enable zone (H2/B4)

Disabled zones are listed in menu H4/U1 from which it is also
possible to get a print-out.
Re-enabling via this menu has higher priority than automatic re-
enabling.
When all zones have been re-enabled, The LED
"General disablements" (L10) will be turned OFF, if there are no other
disablements in the system.
NOTE! It is not possible to collectively re-enable a number of alarm
points (zone-address) that are individually disabled via menu H2/B2.
Text in display
H2 Disable or re-enable
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
B4 Re-enable zone
Re-enable zone 001
zone 002
zone 006
zone 073
Re-enable zone 002
zone 006
zone 073
95
Fault / Disablements
Comments
According to chapter
"Access", see page 85.
If there are no zones to re-
enable, menu B4 will be
shown again. The disabled
zones will be shown in a
list. Use "▼" or "▲" to
select the zone and press
"
".
Re-enable another zone or
press "ESC". Scroll to
another menu or press
"ESC".