Panasonic VL-W1-N Series Setup And Maintenance Manual page 112

Laser welding machine
Table of Contents

Advertisement

Item
Time
T1
Approx. 75 sec.
T2
Approx. 15 sec.
T3
Around 200ms to
max. 1 sec.
T4
T5
10 ms or more
T6
T7
20 to 510 ms
112
Remarks
It is the system startup time. Turn ON the remote mode upon verifying SYSTEM STANDBY
OUT (Y4).
It is the time from turning on LASER SUPPLY IN (X9) to completion of laser pumping.
SHUTTER OPEN OUT (Y10) and SHUTTER CLOSE 1&2 OUT (Shutter close output
terminal No.2, 3) have a delay time of up to one second from turning ON of SHUTTER IN
(X10) for the actual shutter open / close operation time.
SHUTTER OPEN OUT and SHUTTER CLOSE 1&2 OUT will be output by the same
operation, but their output timing has a margin of error.
Setup time of the laser welding machine to start the lasing operation.
• In the laser pumping completed state: Time for data creation. It varies depending on the
quantity of the setting data.
• When the laser pumping is not completed: Time for data creation or time for laser
pumping, whichever is longer.
Keep the ON status for 10 ms or more.
When TRIGGER IN (X6) is accepted, LASING OUT (Y7) is turned ON.
One-shot output. Set the output time on the environment setting screen.
There is a small margin of error for the setting value.
READY OUT (Y6) is not turned ON while LASING END OUT (Y8) is ON.
ME-VLW1N-SM-1