Hitachi Relion 670 Series Applications Manual page 58

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
CT 600/5A
Star Connected
IEC16000137 V1 EN-US
Figure 15:
In the example, everything is done in a similar way as in the above described example (Figure 14).
The only difference is the setting of the parameter CTStarPoint of the used current inputs on the
TRM (item 2 in Figure
CTprim=600A
CTsec=5A
CTStarPoint=FromObject
The ratio of the first two parameters is only used inside the IED. The third parameter as set in this
example will negate the measured currents in order to ensure that the currents are measured
towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the two-phase CT set connected to the
IED as shown in Figure 16.
CT 600/5A
Star Connected
IEC16000138 V1 EN-US
Figure 16:
52
L1
L2
IN
IL2
IL1
Protected Object
Star connected two-phase CT set with its star point away from the protected
object
14
and 15):
L1
L2
IN
IL2
IL1
Protected Object
Star connected two-phase CT set with its star point away from the protected
object and the residual/neutral current connected to the IED
© 2017 - 2023 Hitachi Energy. All rights reserved
IED
2
1
3
BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
IED
3
1
4
5
2
1MRK506375-UEN Rev. N
4
SMAI2
AI2P
AI1
5
AI2
AI3
AI4
AIN
IEC16000137-1-en.vsdx
6
SMAI2
BLOCK
AI2P
^GRP2L1
AI1
5
^GRP2L2
AI2
^GRP2L1L2
AI3
^GRP2N
AI4
AIN
IEC16000138-1-en.vsdx
Railway application RER670
Application manual