TripLockout: Sets the scheme for lockout. Off only activates the circuit breaker lockout output when
the input SETLKOUT is activated. On activates the circuit breaker lockout output and latches the
output TRIP when the input SETLKOUT is activated. The normal selection is Off.
AutoLock: Sets the scheme for lockout. Off only activates lockout through the input SETLKOUT. On
additionally allows activation of lockout from the trip function itself. The normal selection is Off.
tTripMin: Sets the required minimum duration of the trip pulse. It should be set to ensure that the
circuit breaker is opened correctly. Normal setting is 0.150 s.
14.1.4.1
Setting example
Consider a line-to-Line fault in a 15 kV, 15 MVA, 16.7 Hz system.
Table 33:
Name
Rated MVA capacity (SBase)
Rated voltage (UBase)
Rated Current (IBase)
System Frequency
VT ratio
CT ratio
The general setting parameters for PHPIOC and SMPPTRC functions can be set as mentioned in
Table 34
GUID-C320F3F5-17B6-4698-91D8-0B6E12E2E6D0 V1 EN-US
Figure 148:
Table 34:
Setting
Operation
GlobalBaseSel
IP>>
Railway application RER670
Application manual
System details
and
Table
35, respectively, and the connection diagram is shown in
Connection diagram of PHPIOC and SMPPTRC functions
General setting parameters for the PHPIOC function
© 2017 - 2023 Hitachi Energy. All rights reserved
Value
15 MVA
15 kV
1000 A
16.7 Hz
15 kV/110 V
1000/1 A
Description
Operation Off/On
Selection of one of the Global Base Value
groups
Operate phase current level in % of IBase
Section 14
Logic
GUID-999D514E-B6D9-4462-B2BA-0BCDB4CAF3E6 v1
Figure
148.
Default value
On
1
200
295