Hitachi Relion 670 Series Applications Manual page 225

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506375-UEN Rev. N
PROTECTION
xxxx-TRIP
ZCVPSOF-TRIP
SESRSYN-AUTOOK
IEC17000005 V1 EN-US
Figure 80:
12.2.4.2
Auto recloser settings
The settings for the auto recloser are set using the local HMI (LHMI) or PCM600.
This setting guideline describes the settings of the auto recloser using the LHMI.
The settings for the auto recloser are found under Main menu /Settings /IED Settings /Control /
AutoRecloser(79,5(0->1)) /SMBRREC(79,5(0->)):X and have been divided into four different setting
groups: General, CircuitBreaker, DeadTime and MasterSlave.
General settings
Operation: The operation of the auto recloser can be switched On or Off.
ExternalCtrl: This setting makes it possible to switch the auto recloser On or Off using an external
switch via IO or communication ports.
StartByCBOpen: The normal setting Off is used when the function is started by protection trip
signals. If set On the start of the auto recloser is controlled by an circuit breaker auxiliary contact.
LongStartInhib: Usually the protection trip command, used as an auto reclosing start signal, resets
quickly as the fault is cleared. A prolonged trip command may depend on a circuit breaker failing to
clear the fault. A protection trip signal present when the circuit breaker is reclosed will result in a new
trip. The user can set a maximum start pulse duration time tLongStartInh. This start pulse duration
time is controlled by the LongStartInhib setting. When the start pulse duration signal is longer than
set maximum start pulse duration, the auto reclosing sequence interrupts in the same way as for a
signal to the INHIBIT input.
tLongStartInh: The user can set a maximum start pulse duration time tLongStartInh. At a set time
somewhat longer than the auto reclosing dead time, this facility will not influence the auto reclosing.
A typical setting of tLongStartInh could be close to the auto reclosing dead time.
Railway application RER670
Application manual
BIM
INPUT
xx
ON
xx
OFF
xx
BLKON
xx
BLKOFF
xx
INHIBIT
xx
xx
CBREADY
xx
CBCLOSED
xx
RESET
OR
START
STARTHS
SKIPHS
TRSOTF
THOLHOLD
SYNC
RSTCOUNT
Example of I/O-signal connections at an auto reclosing sequence
© 2017 - 2023 Hitachi Energy. All rights reserved
SMBRREC
BLOCKED
SETON
INPROGR
ACTIVE
UNSUCCL
SUCCL
CLOSECB
READY
IPT1
IPT2
IPT3
IPT4
IPT5
Section 12
Control
BOM
OUTPUT
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
IEC17000005-1-en.vsdx
GUID-74980A07-CF89-488F-AB17-E5351D0032EE v1
219