the IED is required. Either FineSyncSource is set to the same source that the merging unit uses, or
the PPS output from the GTM module is used to synchronize the merging unit. If the PPS output from
the GTM module is used to synchronize the merging unit and PTP is not used, the IED does not
know how the merging unit is synchronized and the parameter SyncLostMode must be set to
NoBlock.
408
If the IED is used together with a merging unit and no time synchronization is available,
for example, in the laboratory test, the IED will synchronize to the SV data stream. During
the re-synchronization, the protection functions will be blocked once a second for about
45 ms, and this will continue for up to 10 minutes. To avoid this, configure PTP (IEEE
1588) to On for the access point where the merging unit is configured.