Hitachi Relion 670 Series Applications Manual page 143

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506375-UEN Rev. N
7.4
Underimpedance protection for railway transformers
ZGTPDIS
7.4.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
M
N
7.4.2
Identification
Function description
Underimpedance protection for railway
transformers
7.4.3
Application
ZGTPDIS is generally used as backup protection for faults on the transformer and the associated
transmission lines. These transformers can be classified in two basic categories:
2-phase to 2-phase Interconnecting transformers
2-phase to 1-phase Interconnecting transformers
Railway application RER670
Application manual
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
Addition of one more instance into transformer protection package and setting range
extension for IMin to meet homologation, IEC 61850 LN mapping modification for Str and
Op data objects.
2.2.3
-
2.2.4
-
2.2.4
-
2.2.5
-
2.2.6
-
2.2.6
-
IEC 61850
identification
ZGTPDIS
© 2017 - 2023 Hitachi Energy. All rights reserved
GUID-B8C0A72B-63F2-4DBD-B702-F749C3EBCCC2 v2
GUID-70204B53-E684-46FC-BD5E-7EB9EDBE4E4A v3
GUID-F416AE1B-7588-4D01-99E0-D3924699A481 v2
IEC 60617
ANSI/
identification
IEEEidentificatio
n
21T
Z<
IEC15000305 V1 EN-US
GUID-54FF2835-A45F-4192-BDA8-D15A0C650BB8 v2
Section 7
Impedance protection
137